AIR-COOLED CONDENSING UNITS
(-)ANL-*AZ MODEL SERIES 13 SEER
(-)APL-JAZ MODEL SERIES 14 SEER
(-)APM-JAZ MODEL SERIES 14.5 SEER
INSTALLATION INSTRUCTIONS
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORT TION!
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
WARNING
!
ANT SAFETY INFORMA
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER
INSTALLAT ION, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE
AT TEMPTING INSTALLATION OR OPERATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLAT ION, ADJUSTMENT, SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
[ ] INDICATES METRIC CONVERSIONS
r
efrigerant
ISO 9001:2000
(14.5 SEER MODELS
& 14 OR 13 SEER
MODELS IN CERTAIN
MARKED SYSTEMS)
Vue de la page 0
1 2 3 4 5 6 ... 27 28

Résumé du contenu

Page 1 - INSTALLATION INSTRUCTIONS

92-21354-51-08SUPERSEDES 92-21354-51-07AIR-COOLED CONDENSING UNITS(-)ANL-*AZ MODEL SERIES – 13 SEER(-)APL-JAZ MODEL SERIES – 14 SEER(-)APM-JAZ MODEL S

Page 2 - TABLE OF CONTENTS

10The thermostatic expansion valve is specifically designed to operate with R-410A.R-410A.LOCATIONDo not install the indoor evaporator coil in the ret

Page 3 - UNIT MODEL NUMBER EXPLANATION

115. Capillary Tube Coil:DO NOT exceed the Table values for vertical separation for capillary tube coils.6. Always use the smallest liquid line size p

Page 4

12TUBING CONNECTIONSIndoor evaporator coils have only a holding charge of dry nitrogen. Keep all tubeends sealed until connections are to be made.• Us

Page 5 - CORROSIVE ENVIRONMENT

131/4 000 082411⁄2 Ton 3/8ⴖ 5/16 0 00 0003/8* 0 00 0001/4 0329 55 81 1082 Ton 3/8ⴖ 5/16 0 00 0003/8* 0 00 0001/4 0 14 56 98 N/A N/A21⁄2 Ton 3/8ⴖ 5/16

Page 6 - LOCATING UNIT

14LEAK TESTING• Pressurize line set and coil through service fittings with dry nitrogen to 150 psigmaximum. Leak test all joints using liquid detergen

Page 7 - UNIT MOUNTING

15The installers should balance the air distribution system to ensure proper quiet air-low to all rooms in the home. This ensures a comfortable living

Page 8 - SPECIFICATION OF R-410A:

163. Read and record the indoor ambient wet bulb temperature entering the indoorcoil.4. Use the appropriate charging chart to compare the actual liqui

Page 9 - EVAPORATOR COIL

17DO NOT connect aluminum field wire to the contactor terminals.GROUNDINGA grounding lug is provided near the contactor for a ground wire.CONTROL WIRI

Page 10 - INTERCONNECTING TUBING

18HIGH AND LOW PRESSURE CONTROLS(HPC OR LPC)These controls keep the compressor from operating in pressure ranges which cancause damage to the compress

Page 11 - TUBING INSTALLATION

19HARD START COMPONENTSStart components are not usually required with the scroll compressors used in(-)ANL/(-)APL/(-)APM condensing units, but are ava

Page 12 - TUBING CONNECTIONS

2TABLE OF CONTENTSChecking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Dimensions . . . . . . . . . . .

Page 13 - *Standard Line Size

20ELECTRICAL CHECKS FLOW CHARTUnit Running?NONONONONOYESYESYESYESThermostat Problem?Transformer Problem?Run CapacitorCompressor ContactorHi Pressure C

Page 14 - CHECKING AIRFLOW

21MECHANICAL CHECKS FLOW CHARTUnit Running?YESLow Head PressureLow Suction PressureOpen IPR Valve Dirty EvaporatorInadequate AirflowRestricted Filter-

Page 15 - CHECKING REFRIGERANT CHARGE

22AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPSAIR CONDITIONING SYSTEMTROUBLESHOOTING TIPSSUPERHEAT CALCULATION1. Measure the suction pressure at the s

Page 16 - ELECTRICAL WIRING

23SYMPTOM POSSIBLE CAUSE REMEDYUnit will not run • Power off or loose electrical connection • Check for correct voltage at contactor in condensing uni

Page 17 - CONTROL WIRING

24FIGURE 4SINGLE-PHASE WIRING DIAGRAM

Page 18 - FIELD INSTALLED ACCESSORIES

25FIGURE 5THREE-PHASE WIRING DIAGRAM (C, D & Y VOLTAGES)

Page 22 - SUBCOOLING CALCULATION

FIGURE 1DIMENSIONS AND INSTALLATION CLEARANCESUNIT MODEL NUMBER EXPLANATION3A-00002BOTTOM VIEW SHOWING DRAIN OPENINGS(\\\\\ SHADED AREAS).AA-00001ALLO

Page 23 - TROUBLE SHOOTING CHART

018J*Z 1-60-208/230 9/9 48 0.8 13/13 15/15 20/20 11 [1.02] 1 1900 [897] 79 [2240] 140 [63.5] 155 [70.3]024J*Z 1-60-208/230 13.5/13.5 58.3 0.8 18/18 25

Page 24 - FIGURE 4

GENERALThe information contained in this manual has been prepared to assist in the properinstallation, operation and maintenance of the air conditioni

Page 25 - FIGURE 5

6• Frequent washing of the cabinet, fan blade and coil with fresh water will removemost of the salt or other contaminants that build up on the unit.•

Page 26 - FIGURE 6

7STEP 4: Drill four pilot holes in pad, ensuring that the hole is at least 1/4” deeperthan the concrete screw being used.STEP 5: Center basepan over p

Page 27

8REFRIGERANT CONNECTIONSAll units are factory charged with Refrigerant 410A. All models are supplied withservice valves. Keep tube ends sealed until c

Page 28 - 28 CM 0908

9Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and itssaturation pressure at 77°F is 224.5 psig.Composition: R-410A is an az